TMV testing and servicing requirements

The short answer

Thermostatic mixing valves delivering warm water in aged care, hospitals, schools, childcare and disability accommodation must be tested and serviced every 12 months under AS 4032.3, with a major service every 5 years. There is no regulator to lodge with, so the record you keep is the compliance.

StandardAS 4032.3:2022
Frequency12 months, plus a 5-yearly major service
LodgementNone, the record is kept by you and the facility

Why the record matters more here than anywhere else

There is no authority to submit a TMV test to. That sounds easier, but it means the test record is the entire evidence trail. Facility managers, aged care operators and health departments ask for it at accreditation and audit time, and if the record is not there the test may as well not have happened. One report per valve, and sites often have dozens.

The temperatures you are working to

The mixed warm water at the outlet should sit between 40.5 and 43.5°C after about five minutes of stabilised flow, and it must not exceed 45°C. AS/NZS 3500.4 sets the maximum delivery temperatures that sit behind this: 50°C at sanitary fixtures generally, and 45°C in early childhood centres, schools, and nursing homes and aged care.

The fail-safe test is the important one

Anyone can measure an outlet temperature. The test that matters is the thermal shut-off. Isolate the cold supply and the valve must shut off or drop to a trickle, and it should do it within about 4 seconds, with the outlet not exceeding 46°C while it happens. Then restore the cold and confirm the valve recovers and delivers stable warm water back in range. That is the test that proves the valve will not scald someone when the cold supply drops.

Annual test versus major service

The 12 month visit is a test and service: strainers cleaned, non-return valves checked, temperatures verified, valve tagged. The 5 year major service replaces the thermostat or cartridge and the o-rings and seals, and in practice many just replace the cartridge or the whole valve. Worth tracking both dates separately, because they fall due independently.

Who is responsible for what

The facility owner or operator is responsible for having its TMVs tested and maintained. The work must be done by a plumber holding the TMV endorsement. The servicing plumber keeps the AS 4032.3 test record and the facility keeps a copy, because those are what auditors ask to see.

What the report should record

What commonly goes wrong

Do the check on your phone, hand over the report before you leave

Safety Check Pro walks you through the checkpoints, records your test results and photos, and produces a branded PDF report with your own logo on it. Works offline, syncs when you have signal.

See how it works All report types

Free plan includes 4 reports a month. No card needed to start.

Common questions

How often do TMVs need to be tested?

Every 12 months for the full test and service, with a major service every 5 years to replace the thermostat, o-rings and seals.

What temperature should a TMV deliver?

Between 40.5 and 43.5°C at the outlet after stabilised flow, and never above 45°C. AS/NZS 3500.4 caps delivery at 45°C in early childhood centres, schools, nursing homes and aged care.

Do TMV test results have to be lodged anywhere?

No. There is no regulator lodgement. The AS 4032.3 record is kept by the servicing plumber and the facility, and produced at audit.

Who can service a TMV?

A plumber holding the TMV endorsement. The test instrument also needs a current calibration date recorded.

More Plumbing & Gas guides

Last reviewed: September 2026. General information for tradespeople, not legal advice. Standards and regulations change. Governing references for this page: AS 4032.3:2022; AS/NZS 3500.4; NSW Health warm water approval specification for health facilities. Confirm the current position with the facility's own accreditation body or state health department before you rely on it.